25
OverSpeed Limit
Allen-Bradley · PowerFlex 700
Was bedeutet 25 ?
Functions like Slip Compensation or Bus Regulation have attempted to add an output frequency adjustment greater than that programmed in [Overspeed Limit]. This occurs when the drive tries to exceed its configured maximum speed due to an external force (overhauling load) or control algorithm, potentially leading to instability.
Häufige Ursachen
- Motor speed exceeds the configured overspeed limit (e.g., P3-02).
- Runaway motor condition due to loss of control.
- Incorrect encoder feedback indicating higher speed than actual.
- External control signal commanding excessive speed.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Remove excessive load or overhauling conditions on the motor.
- 2
Increase the value of the [Overspeed Limit] parameter.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026