Übersetzen...
F42

Phase UW Short

Allen-Bradley · PowerFlex 4 Adjustable Frequency

Was bedeutet F42 ?

A short circuit condition has been detected between motor phases U and W, or in the wiring connecting drive output terminals U and W to the motor. This indicates an unintended low-resistance path between these phases.

Häufige Ursachen

  • Short circuit between phase U and phase W windings in the motor.
  • Internal short circuit in the drive's output power module.
  • Power cable damage causing conductors U and W to short.
  • Incorrect motor connection or wiring error.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Disconnect the motor from the drive output terminals (U, V, W).

  2. 2

    Measure resistance between drive output terminals U and W with the motor disconnected; expect an open circuit (infinite resistance) if no internal drive fault.

  3. 3

    Measure resistance between motor phases U and W; expect a low resistance reading (continuity across the motor winding).

  4. 4

    Inspect the wiring between drive output terminals U, W and motor phases U, W for any physical damage or direct short circuits.

Alle Codes in diesem Handbuch durchsuchen (24)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Allen-Bradley PowerFlex 4 Adjustable Frequency