F011
Data Type Mismatch
Allen-Bradley · Logix and SLC PLC
Was bedeutet F011 ?
This error occurs when the data type requested by an operation does not match the actual data type available at the specified memory location. This leads to an inability to correctly interpret or process the data.
Häufige Ursachen
- Attempting to read a floating-point value as an integer.
- Incorrect tag declaration for a data point.
- Communication protocol expecting a different data format.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Connect to the PLC via the programming software and identify the specific instruction or routine that generates the F011 Data Type Mismatch error.
- 2
Inspect the data type definitions of all tags referenced within the identified instruction or routine, verifying they align with the expected data types.
- 3
Cross-reference all usages of the involved tags throughout the PLC program to ensure consistent data type handling across all operations.