CVFaulted (Status1.2)

Control Variable (CV) Health Bad

Allen-Bradley · Logix 5000 Controllers

Was bedeutet CVFaulted (Status1.2) ?

This fault indicates that the Control Variable (CV) health is bad. This can be due to poor CV value quality, an invalid CV value, or a communication fault affecting the CV output. When true, CVFault indicates an error on the output module, and the PIDE instruction sets the appropriate bit in Status. The equivalent Sts_CVBad in the PPID instruction will also be set if Inp_CVIOFault is true.

Häufige Ursachen

  • CV value quality is bad or invalid (e.g., Inf, -Inf, NaN)
  • Communication fault with the CV output module
  • Analog output module fault status indicates an error (Inp_CVIOFault = 1 for PPID)

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the analog output signal from the CV output module (e.g., terminals) using a multimeter or process calibrator

  2. 2

    Check the communication status of the CV output module in the I/O tree, looking for module faults

  3. 3

    Confirm the CV output module is healthy and not reporting internal faults via its diagnostics

  4. 4

    Verify that the Inp_CVIOFault input (for PPID) is not actively being driven high by external conditions or logic

Alle Codes in diesem Handbuch durchsuchen (17)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes