24582
Program Already Owns Equipment Phase
Allen-Bradley · Logix 5000 Advanced Process Control and Drives
Was bedeutet 24582 ?
The PATT instruction tried to take ownership of the equipment phase, but the executing program already possesses ownership. This often occurs when the instruction is repeatedly executed.
Häufige Ursachen
- The PATT instruction is continuously executed without prior relinquishment of ownership, or without checking for existing ownership.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Ensure the PATT instruction is executed only once per state transition, or limit its execution to a single scan.
- 2
Implement logic to check for existing ownership (e.g., using this result code 24582) before attempting to re-take ownership.
- 3
Verify that a Detach from Equipment Phase (PDET) instruction is used to release ownership when program control is no longer required.