Übersetzen...
CJChxx.Uncertain

Cold Junction Data Uncertain (5069-IY4, 5069-IY4K)

Allen-Bradley · Compact 5000 I/O Analog Modules

Was bedeutet CJChxx.Uncertain ?

This boolean tag indicates that the cold junction data for a specific channel (xx) can be inaccurate, though the exact degree of inaccuracy is not known. A value of 1 means the data is uncertain. The tag automatically resets to 0 once the underlying condition is resolved.

Häufige Ursachen

  • Cold junction data signal slightly outside the channel operating range
  • Cold junction channel (CJChxx) is slightly over temperature
  • Invalid sensor offset value configured for the cold junction channel
  • Calibration fault on the cold junction channel
  • Calibration is currently in process on the cold junction channel

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the cold junction data signal is within the specified channel operating range.

  2. 2

    Check the module's operating environment temperature and the cold junction temperature for any slight over-temperature conditions.

  3. 3

    Review the sensor offset value configured for the cold junction channel (CJChxx) in the module configuration.

  4. 4

    Check the calibration status of the cold junction channel (CJChxx) in the Logix Designer application.

  5. 5

    Wait for any ongoing calibration process on the cold junction channel (CJChxx) to complete.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Allen-Bradley Compact 5000 I/O Analog Modules