Error Applying Mint Motion Library Command

ABB · Application Error ABB Motion Drives Error trouble shoo

Was bedeutet b06410 ?

This error occurs during or after a firmware upgrade when parameters are re-instated. It typically indicates that the new firmware version has introduced a new parameter that was not present in the old parameter file, preventing proper configuration.

Häufige Ursachen

  • Incompatibility between an old parameter file and a newly upgraded firmware version due to new parameters.
  • The drive's parameter file (PTX) is corrupted or contains invalid data for the new firmware.
  • Incomplete or failed firmware upgrade process.
  • Attempting to apply parameters from a different drive model or firmware version.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Connect Mint WorkBench to the drive, access the command line, and enter the "FDF" or "FACTORYDEFAULTS" command.

  2. 2

    Power cycle the drive (note that the IP address will return to 192.168.0.1 after factory defaults).

  3. 3

    Re-commission the drive from scratch using Mint Workbench, ensuring all parameters are set correctly for the new firmware.

  4. 4

    Alternatively, download a previously saved parameter (PTX) file that is known to be compatible with the current firmware version.