10039

Resolver signals lost or incorrect (_ecRESOLVER_SIGNAL_LOSS)

ABB · Application Error ABB Motion Drives Error trouble shoo

Was bedeutet 10039 ?

An error has occurred when using the Resolver Adapter (OPT-MF-201 or FB-03). The error is caused by the loss of resolver signals, indicating issues with the wiring to the motor's feedback device, the motor connector, or connections inside to the adapter.

Häufige Ursachen

  • Damaged or improperly connected wiring to the motor's resolver feedback device.
  • Integrity issues with the motor connector, such as loose pins or corrosion.
  • Faulty connections or components within the Resolver Adapter (OPT-MF-201 or FB-03).
  • Improper earthing or shielding of the resolver cable, leading to signal interference.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the wiring from the motor's resolver feedback device to the Resolver Adapter and ensure all connections are secure and correct.

  2. 2

    Inspect the integrity of the motor connector for damage, bent pins, or proper seating.

  3. 3

    Examine the connections inside the Resolver Adapter (OPT-MF-201 or FB-03) for any loose or faulty wiring.

  4. 4

    Connect to the drive with Mint Workbench, go to "Parameters > Encoder > Channel 0 > Encoder Parameter(Encoder0, Fault Register)" and check its value for more specific error information (if not 0).

  5. 5

    Verify all earthing and shielding connections are as per the drive installation manual to prevent noise.