10036

Encoder reading wrong or Hall fault

ABB · Application Error ABB Motion Drives Error trouble shoo

Was bedeutet 10036 ?

The drive (MotiFlex e100, MotiFlex e180, MicroFlex e190) has detected that the measured Hall transition angle differs from the electrical angle used in the control by at least 70 degrees, indicating a significant discrepancy in position feedback.

Häufige Ursachen

  • Incorrect physical installation or mounting of the encoder, leading to misalignment.
  • A faulty encoder or damaged internal Hall sensors.
  • Incorrect encoder type selection in the drive's parameter configuration.
  • Wiring errors, loose connections, or improper shielding/earthing of the encoder cable causing signal integrity issues.
  • Significant electrical noise or interference on the encoder signals.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the physical installation and mounting of the encoder for proper alignment, secure attachment, and ensure it is not loose or slipping.

  2. 2

    Verify that the encoder type selected in the drive's parameters matches the actual installed encoder model.

  3. 3

    Inspect all encoder wiring for correct connections, continuity, and ensure all earthing and shielding are applied strictly according to the drive installation manual.

  4. 4

    Use Mint Workbench to scope "Encoder Hall State" and "Encoder" signals to visually identify any anomalies or inconsistencies in the feedback.

  5. 5

    Perform a motor ID run or encoder self-test (if available) to verify the drive's ability to correctly interpret encoder feedback.

Alle Codes in diesem Handbuch durchsuchen (58)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026