Übersetzen...
FF85

Motor Torque Limit

ABB · ACS800 Standard Firmware

Was bedeutet FF85 ?

The drive is actively limiting motor torque based on the calculated motor pull-out torque limit and the minimum/maximum torque limits defined by parameters 20.13 (MIN TORQ SEL) and 20.14 (MAX TORQ SEL). This is an informative alarm (programmable Fault Function 30.23, bit 3: MOT_TORQ_LIM_IND) indicating the drive is operating at its configured torque boundaries.

Häufige Ursachen

  • Motor output torque has exceeded its configured limit (P4-02).
  • Excessive load or stall condition applied to the motor shaft.
  • Mechanical binding or jamming in the driven equipment.
  • Control loop instability causing transient torque spikes.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check parameter 20.13 (MIN TORQ SEL) and 20.14 (MAX TORQ SEL) settings to ensure they are appropriate for the application.

  2. 2

    Review Fault Function parameters, specifically 30.23 (LIMIT WARNING), which activates this alarm, to understand its configuration.

  3. 3

    If LIMIT WORD 1 bit 0 (TORQ MOTOR LIM) is active, verify motor parameter settings in group 99 (START-UP DATA) and confirm that an ID run has been completed successfully.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes