4313
Motor 2 Temperature Alarm
ABB · ACS800 Standard Firmware
Was bedeutet 4313 ?
The measured temperature of motor 2 has exceeded the alarm limit set by parameter 35.05. This indicates a potential overheating condition specific to motor 2, requiring attention to prevent damage.
Häufige Ursachen
- Temperature alarm threshold reached for Motor 2.
- Motor 2 experiencing excessive heat.
- Faulty temperature sensor on Motor 2.
- Overload or inadequate cooling for Motor 2.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the alarm limit value set in parameter 35.05 to ensure it is appropriate for the motor.
- 2
Verify that the actual number of temperature sensors connected to motor 2 corresponds to the value set by the parameter.
- 3
Stop motor 2 and allow it to cool down to a safe operating temperature.
- 4
Ensure proper cooling for motor 2 by checking its cooling fan for operation and cleaning any cooling surfaces.