Übersetzen...
A982

External warning 2

ABB · ACS580

Was bedeutet A982 ?

An external device configured as External Event 2 (parameters 31.03 and 31.04) has generated a warning. This indicates a potential issue with external equipment or sensors that should be investigated, though it may not cause an immediate drive trip. Addressing warnings proactively prevents escalation to faults.

Häufige Ursachen

  • Elevated temperature on an external motor bearing, activating a thermal switch connected to the drive's configured digital input (P31.03, P31.04).
  • Low fluid level in an external process tank, causing a level switch to trigger a warning signal on the digital input.
  • Minor mechanical obstruction or drag in the connected machinery, increasing motor current marginally and triggering an external current monitoring relay set to a warning threshold.
  • Loose wire connection or corrosion on the external sensor's output terminal, leading to an intermittent warning signal on the input.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Determine the specific external sensor or device linked to the digital input configured by P31.03 (External Event 2 source).

  2. 2

    2. Use a multimeter to verify the voltage level at the drive's digital input terminal corresponding to the external warning.

  3. 3

    3. Inspect the external sensor and its associated process (e.g., temperature, pressure, level) for any out-of-range conditions that would trigger the warning.

  4. 4

    4. Confirm that P31.03 (External Event 2 source) and P31.04 (External Event 2 action) are set to the correct signal source and warning response.

  5. 5

    5. Clean and re-terminate the wiring connection from the external device to the drive's input terminal to eliminate potential intermittent contact issues.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes