External warning 1
ABB · ACS580
Was bedeutet A981 ?
An external device configured as External Event 1 (parameters 31.01 and 31.02) has generated a warning. This indicates a potential issue with external equipment or sensors that should be investigated, though it may not cause an immediate drive trip. Addressing warnings proactively prevents escalation to faults.
Häufige Ursachen
- Pre-alarm condition (e.g., high temperature approaching limit, low pressure warning) on the external device connected to the digital input configured by P31.01 and P31.02.
- Intermittent signal loss or noise on the sensor feedback wire from the external device, causing a transient warning trigger on the configured digital input.
- Degradation of the external sensor (e.g., proximity switch failing, pressure transducer drifting) providing an out-of-spec but non-critical signal to the drive.
- Inappropriate threshold setting for the warning trigger in the external device, leading to nuisance warnings under normal operating conditions.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Identify the external device connected to the digital input specified by P31.01 (External Event 1 source).
- 2
2. Measure the signal voltage at the digital input terminal for the external warning to confirm its state (e.g., 24VDC, 0VDC).
- 3
3. Examine the external device's status and operation for any pending issues or warning indicators.
- 4
4. Review P31.01 (External Event 1 source) and P31.02 (External Event 1 action) to ensure the drive's response to the external signal is correctly configured for a warning.
- 5
5. Log the time and duration of the warning to correlate with external process events or equipment cycles.