Übersetzen...
3381

Output phase loss

ABB · ACS580

Was bedeutet 3381 ?

The drive has detected a loss of one or more phases between its output terminals and the connected motor. This typically results from a broken cable, loose connection, or open circuit protection, which can lead to motor instability, overheating, or failure if ignored.

Häufige Ursachen

  • Open circuit in one or more motor cable conductors due to mechanical damage or excessive bending fatigue.
  • Loose terminal connection on drive output terminals (U, V, W) or motor terminal box (T1, T2, T3).
  • Blown fuse or tripped thermal overload relay in the motor circuit external to the drive output.
  • Internal winding discontinuity in the motor itself (e.g., broken stator winding).
  • Incorrectly sized or faulty output contactor (if present) failing to close all poles.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    De-energize the drive. Measure resistance between drive output terminals (U-V, V-W, W-U) with the motor connected; expect balanced readings.

  2. 2

    Isolate the motor. Measure insulation resistance of each motor winding to ground and between phases using a megohmmeter (1000V).

  3. 3

    Verify continuity of each individual motor cable conductor from drive output to motor terminal using a multimeter.

  4. 4

    Inspect and re-torque all motor cable connections at the drive output terminals (e.g., U, V, W) and motor terminal box.

  5. 5

    If external protection is used, verify continuity and proper setting of motor fuses or thermal overload relay (e.g., set to motor rated current).

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes