7
DC overvoltage
Danfoss · VLT HVAC-FC 102 Frequency Converter
What does 7 mean?
If the intermediate circuit voltage exceeds its critical limit, the frequency converter will trip after a time delay. This fault often occurs due to regenerative braking, sudden load changes, or issues with the mains supply. Repeated overvoltage trips can damage the drive's power components.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Increase the trip delay at inverter fault (14-26) or enable kinetic back-up (14-10) to ride through transient overvoltage conditions or power sags.
Source: Danfoss VLT HVAC-FC 102 Frequency Converter