Motor thermistor over temp
Danfoss · VLT HVAC-FC 102 Frequency Converter
What does 11 mean?
The motor thermistor indicates an over-temperature condition, or the thermistor itself may be disconnected or improperly wired. This suggests the motor is overheating, which can lead to severe damage if left unaddressed. Select whether the frequency converter issues a warning or an alarm in 1-90 Motor Thermal Protection.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
For digital inputs (18/19), check the thermistor connection between 18 or 19 (PNP only) and terminal 50, and confirm parameter 1-93 Thermistor Source is correctly configured.
Source: Danfoss VLT HVAC-FC 102 Frequency Converter