ALARM 9
Inverter overload
Danfoss · VLT HVAC Drive High Power
What does ALARM 9 mean?
The frequency converter has been operating with more than 100% overload for too long, triggering a warning at 98% and an alarm at 100%. The unit will trip, and cannot be reset until the internal thermal counter falls below 90%. Prolonged overload can severely damage the inverter's power components.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Monitor the thermal frequency converter load value on the LCP; ensure it decreases when running below the continuous current rating.
Source: Danfoss VLT HVAC Drive High Power