WARNING/ALARM 9
Inverter overloaded
Danfoss · VLT HVAC Basic FC 101
What does WARNING/ALARM 9 mean?
The frequency converter is experiencing an overload, with the internal thermal counter indicating that current levels are exceeding 100% for an extended duration. This activates electronic thermal protection, issuing a warning at 90% and an alarm trip at 100% to prevent damage. The drive cannot be reset until the counter falls below 90%.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Inspect for any mechanical binding, seized bearings, or other issues in the driven equipment causing excessive load.
- 4
Allow the frequency converter to cool down; it cannot be reset until the internal thermal counter drops below 90%.
Source: Danfoss VLT HVAC Basic FC 101