25
Brake resistor short circuit
Danfoss · VLT AutomationDrive FC 301/302
What does 25 mean?
The brake resistor is monitored during operation. If a short circuit occurs, the brake function is disabled and the warning appears. The frequency converter is still operational, but without the brake function.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Replace the brake resistor, referring to parameter 2-15 Brake Check for verification after replacement.
Source: Danfoss VLT AutomationDrive FC 301/302