13
Overcurrent
Danfoss · VLT AutomationDrive FC 301/302
What does 13 mean?
The inverter peak current limit, approximately 200% of the rated current, has been exceeded. This warning typically lasts about 1.5 seconds before the frequency converter trips and issues an alarm. Common causes include shock loading, rapid acceleration with high-inertia loads, or issues during kinetic back-up.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check that all motor data parameters (1-20 to 1-25) are correctly entered and configured in the drive.
Source: Danfoss VLT AutomationDrive FC 301/302