#14
Earth (ground) fault
Danfoss · FC302 AC Drives Programming Guide
What does #14 mean?
An earth (ground) fault has been detected, indicating an unintended current path from a phase conductor to the ground. This usually points to damaged insulation in the motor windings or associated cabling, posing a significant safety hazard and a risk of severe damage to the drive or compressor components.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If the measured insulation resistance is less than 500 KΩ, the fault is likely in the compressor; replace the compressor unit.
- 4
If the measured insulation resistance is greater than 500 KΩ, the fault is likely within the drive or its internal wiring; replace the drive unit.
Source: Danfoss FC302 AC Drives Programming Guide