FB ESTOP Bit 1
E-Stop Discrepancy Error - Input Group 2
Beckhoff · TwinSAFE Logic FB
What does FB ESTOP Bit 1 mean?
A discrepancy has been detected between the two channels of input group 2 for the FB ESTOP. This indicates that the redundant E-Stop input signals are not in agreement, suggesting a potential failure of one channel, a wiring issue, or an incorrect switching sequence. This will prevent the E-Stop function from operating safely and halt the machine.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Review the discrepancy time parameter for E-Stop input group 2 in the FB ESTOP configuration; adjust if the application legitimately has different timing requirements.
- 4
Monitor the individual input channels for group 2 in real-time using diagnostics to identify which channel is deviating or delayed.
Source: Beckhoff TwinSAFE Logic FB