Diag3:lit, Diag4:flashing
Internal Terminal Error (μC1)
Beckhoff · EL6900 Operating Instructions
What does Diag3:lit, Diag4:flashing mean?
This LED combination (Diag 3 lit, Diag 4 flashing) indicates an internal error related to microcontroller 1 (μC1) of the terminal. This is a global fault, leading to the shutdown of the terminal. Such errors typically necessitate inspection by the manufacturer.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Access the TwinCAT System Manager to check for any additional diagnostic messages or system events logged by the EL6900 prior to the shutdown.
Source: Beckhoff EL6900 Operating Instructions
Open Manual (Page 54)