P3 240 V AC Loss
Allen-Bradley · PowerFlex 750 AC Drive
What does 11319 mean?
240V AC input power was lost on port 3 while the drive was in an active state (e.g., MCS opening, closing, or closed). This causes the drive to cease operation.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check any upstream circuit breakers, fuses, or contactors related to the 240V AC supply for tripping or failure.
- 4
Ensure the molded case switch (MCS) and its associated control circuitry are operating correctly and maintaining a closed state when active.
- 5
Monitor the AC line voltage at the drive input terminals using a multimeter to confirm its presence and stability.
Source: Allen-Bradley PowerFlex 750 AC Drive