11315

P3 Bus Dip

Allen-Bradley · PowerFlex 750 AC Drive

What does 11315 mean?

The DC bus voltage on port 3 has dipped more than 180V below the drive's bus memory when the drive is offline or in stand-alone mode. This indicates an unstable DC bus voltage, which can affect drive reliability.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Verify the drive's bus memory settings and internal voltage references against actual measured bus voltage readings.

  2. 4

    Ensure the drive is properly sized for the application's connected load to prevent excessive and frequent bus voltage dips.

  3. 5

    Check the health of the DC bus capacitors, as degraded capacitors can lead to poor voltage ripple suppression.

Source: Allen-Bradley PowerFlex 750 AC Drive