11115
P1 Bus Dip
Allen-Bradley · PowerFlex 750 AC Drive
What does 11115 mean?
The DC bus voltage on port 1 has dipped more than 180V below the drive's bus memory when the drive is offline or in stand-alone mode. This indicates an unstable DC bus voltage, which can affect drive reliability.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Verify the drive's bus memory settings and internal voltage references against actual measured bus voltage readings.
- 4
Ensure the drive is properly sized for the application's connected load to prevent excessive and frequent bus voltage dips.
- 5
Check the health of the DC bus capacitors, as degraded capacitors can lead to poor voltage ripple suppression.
Source: Allen-Bradley PowerFlex 750 AC Drive