10338

I3 Powering Down

Allen-Bradley · PowerFlex 750 AC Drive

What does 10338 mean?

This fault is asserted when the DC bus voltage drops to 80% of its rated value on port 3. This indicates a significant loss of DC bus voltage which can lead to drive shutdown and loss of control.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Inspect the DC bus capacitors for any signs of degradation, bulging, or leakage that would indicate reduced capacitance.

  2. 4

    Verify the proper operation of the drive's power supply monitoring circuitry to ensure accurate voltage readings.

  3. 5

    Reduce the drive load if the powering down event frequently correlates with high load conditions on the motor.

Source: Allen-Bradley PowerFlex 750 AC Drive