10138
I1 Powering Down
Allen-Bradley · PowerFlex 750 AC Drive
What does 10138 mean?
This fault is asserted when the DC bus voltage drops to 80% of its rated value on port 1. This indicates a significant loss of DC bus voltage which can lead to drive shutdown and loss of control.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Inspect the DC bus capacitors for any signs of degradation, bulging, or leakage that would indicate reduced capacitance.
- 4
Verify the proper operation of the drive's power supply monitoring circuitry to ensure accurate voltage readings.
- 5
Reduce the drive load if the powering down event frequently correlates with high load conditions on the motor.
Source: Allen-Bradley PowerFlex 750 AC Drive