F81
Communication Loss
Allen-Bradley · PowerFlex 40 Adjustable Frequency AC Drive
What does F81 mean?
This fault indicates a loss of communication with the drive's control source, possibly due to an adapter disconnection, wiring issue, or a communication timeout. This fault's action (fault, stop, continue) can be configured by A105.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If an adapter was intentionally disconnected, turn off the fault action by setting A105 [Comm Loss Action] to a value other than “Fault” (0).
- 4
Replace wiring, port expander, adapters, or the complete drive as required if communication issues persist after checking connections.
Source: Allen-Bradley PowerFlex 40 Adjustable Frequency AC Drive
Open Manual (Page 17)