F63
SW OverCurrent
Allen-Bradley · PowerFlex 4 Adjustable Frequency AC Drive
What does F63 mean?
A software-detected overcurrent condition has occurred, meaning the instantaneous output current has exceeded the trip level configured by parameter A098 [SWCurrent Trip]. This is a configurable threshold for current monitoring.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Increase acceleration time (parameter P039 [Accel Time1] or A067 [Accel Time2]) to reduce peak currents during motor startup.
Source: Allen-Bradley PowerFlex 4 Adjustable Frequency AC Drive