F39
Phase V to Gnd
Allen-Bradley · PowerFlex 4 Adjustable Frequency AC Drive
What does F39 mean?
A grounded phase condition has been detected specifically on motor phase V or in the wiring connecting drive output terminal V to the motor. This indicates a direct short path to ground.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Measure insulation resistance between motor phase V and the motor frame using a megger at 500VDC; expect a reading greater than 1 MΩ.
- 4
Inspect the wiring connecting drive output terminal V and motor phase V for any physical damage or signs of insulation breakdown.
Source: Allen-Bradley PowerFlex 4 Adjustable Frequency AC Drive
Open Manual (Page 15)