Scanner Not Available to 1771 Rack Adapter
Allen-Bradley · Logix and SLC PLC
What does F016 mean?
This fault occurs when the communication scanner is unable to establish or maintain communication with a 1771 rack adapter. This prevents I/O modules in the 1771 rack from being read or written to.
Common Causes
- Physical disconnection of the scanner from the 1771 rack adapter.
- 1771 rack adapter power failure or hardware fault.
- Incorrect configuration of the scanner or adapter module.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify power supply voltage to the 1771 rack adapter and the 1771 I/O rack backplane against specified nominal values.
- 2
Inspect all communication cabling between the communication scanner module and the 1771 rack adapter for damage, proper termination, and secure connections.
- 3
Check status indicators (e.g., COM, OK, FAULT LEDs) on both the communication scanner module and the 1771 rack adapter for diagnostic information.
- 4
Verify the communication parameters and addressing configured in the PLC's scanner module match the physical DIP switch settings or configuration of the 1771 rack adapter.