F016

Scanner Not Available to 1771 Rack Adapter

Allen-Bradley · Logix and SLC PLC

What does F016 mean?

This fault occurs when the communication scanner is unable to establish or maintain communication with a 1771 rack adapter. This prevents I/O modules in the 1771 rack from being read or written to.

Common Causes

  • Physical disconnection of the scanner from the 1771 rack adapter.
  • 1771 rack adapter power failure or hardware fault.
  • Incorrect configuration of the scanner or adapter module.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify power supply voltage to the 1771 rack adapter and the 1771 I/O rack backplane against specified nominal values.

  2. 2

    Inspect all communication cabling between the communication scanner module and the 1771 rack adapter for damage, proper termination, and secure connections.

  3. 3

    Check status indicators (e.g., COM, OK, FAULT LEDs) on both the communication scanner module and the 1771 rack adapter for diagnostic information.

  4. 4

    Verify the communication parameters and addressing configured in the PLC's scanner module match the physical DIP switch settings or configuration of the 1771 rack adapter.

Browse all codes in this manual (39)
Verified technical data. Last updated: March 2026