Channel Data Potentially Inaccurate
Allen-Bradley · Compact 5000 I/O Analog Modules
What does I.Chxx.Uncertain mean?
This input tag, when set to 1, indicates that channel xx data might be inaccurate, but the degree of inaccuracy is unknown. While not a definitive fault, it suggests potential data integrity issues, and the data should generally not be used for control. The tag typically resets to 0 after a small delay once the condition is removed.
Common Causes
- The data signal is slightly outside the channel's normal operating range.
- The module or channel is operating slightly over its specified temperature.
- An invalid Sensor Offset value is configured for channel xx.
- A calibration fault occurred on channel xx.
- Calibration is currently in process on channel xx, or an active calibration on another module channel is affecting it.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure the input/output signal for channel xx to confirm it is within the expected operating range.
- 2
Check the ambient temperature at the module installation location.
- 3
Verify the O.Chxx.SensorOffset tag setting for channel xx in the Logix Designer application.
- 4
Check the module status in Logix Designer application for any active or recent calibration faults.
- 5
Confirm if any calibration processes are active on the module or other channels.