FF82
Choke Overtemperature
Allen-Bradley · ABB ACS800 Standard Firmware
What does FF82 mean?
The drive output filter (choke) has an excessive temperature. This supervision function is typically used in step-up drives and indicates potential overheating due to restricted airflow, a faulty filter fan, or high ambient temperatures, risking damage to the filter components.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Verify that the filter fan rotates in the correct direction and that air flows freely through the filter and drive vents.
Source: ABB ACS800 Standard Firmware
Open Manual (Page 241)