8110
Analog Input Below Minimum
Allen-Bradley · ABB ACS800 Standard Firmware
What does 8110 mean?
An analog input signal (e.g., 0-10V, 4-20mA) has fallen below its configured minimum limit, which must be set to 0.5V (1 mA) or above in parameter group 13. Depending on parameter 30.01 (AI<MIN FUNCTION), the drive may trip, set a constant speed (12.16), or freeze at the last operating speed.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Review parameter settings in group 13 (ANALOGUE INPUTS) to confirm the minimum limit is configured correctly, typically 0.5V (1mA) or above.
Source: ABB ACS800 Standard Firmware