3220

DC UNDERVOLT

Allen-Bradley · ABB ACS800 Standard Firmware

What does 3220 mean?

The intermediate circuit DC voltage is insufficient, which can be caused by a missing supply voltage phase, a blown input fuse, or an internal fault within the rectifier bridge. The DC undervoltage trip limit is 0.6 × 1.35 × U1min, corresponding to 307 VDC for 400 V and 500 V units, and 425 VDC for 690 V units. This fault is associated with bit 2 of Fault Word 2 (3.06 FW 2).

Source: ABB ACS800 Standard Firmware
Open Manual (Page 242)