FF52

NO MOT DATA

ABB · ACS800

What does FF52 mean?

This fault indicates that essential motor data parameters have not been entered into the ABB ACS800 drive, or the entered data is inconsistent with the connected motor or inverter. Without correct motor data, the drive cannot operate optimally or safely.

Common Causes

  • Required motor parameters (e.g., nominal voltage, current, frequency, speed, power) are missing or set to default values.
  • Entered motor data is incompatible or inconsistent with the specifications of the connected motor or the ACS800 drive.
  • Motor data entry was incomplete during the initial setup or commissioning phase.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check motor data parameters 99.04 through 99.09 and ensure all required values are entered correctly according to the motor nameplate.

  2. 2

    Verify that the entered motor data is compatible with the connected ABB ACS800 drive's specifications.

  3. 3

    Perform an auto-tune procedure (if supported and applicable) after ensuring basic motor parameters are correctly entered.

  4. 4

    Confirm that the motor is correctly wired to the drive and that no phases are missing.

Browse all codes in this manual (33)
Verified technical data. Last updated: March 2026