13
Channel test pulse cross-talk error
ABB · PB610 Panel Builder 600 Programming Software
What does 13 mean?
Cross-talk was detected during the test pulse operation on a safety I/O channel, indicating unwanted signal interference between channels. This can be caused by improper shielding, close proximity of signal wires, or a faulty sensor/module. This is a severity 3 error.
Repair Steps
- 1
Check the wiring connected to the safety I/O module channel for proper separation and shielding.
- 2
Inspect the sensor connected to the channel for potential internal short circuits or malfunctions.
- 3
If the error persists after verifying wiring and sensor, replace the I/O module.
Verified technical data. Last updated: March 2026
Source: ABB PB610 Panel Builder 600 Programming Software