AE02
Earth leakage
ABB · ACS880 Primary Firmware
What does AE02 mean?
The supply unit generates a warning when an earth fault or current unbalance is detected. This indicates a potential insulation issue within the supply unit's power circuit or its input cabling, requiring attention to prevent a full fault trip or damage.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Measure insulation resistance on the supply side components (e.g., input reactor, filter) and input cabling with a megohmmeter.
- 4
Review parameter 31.120 (LSU earth fault) settings for the supply unit's earth fault detection sensitivity.
Source: ABB ACS880 Primary Firmware