FA81

Safe torque off 1

ABB · ACS580 General Purpose Drive

What does FA81 mean?

An asymmetric loss of one of the Safe Torque Off (STO) signals has occurred (e.g., IN1 lost while IN2 is present). This is interpreted as a malfunction in the safety circuit and causes the drive to trip. The drive will not start until both STO signals are restored and all related faults are reset.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Check the value of parameter 95.04 (Control board supply) to ensure stable power to the control board.

  2. 4

    After resolving the cause, reset the drive from an appropriate source (e.g., control panel, digital input).

Source: ABB ACS580 General Purpose Drive