A793

Brake Resistor Excess Temperature

ABB · ACS580 General Purpose Drive

What does A793 mean?

The temperature of the brake resistor has exceeded its configured warning limit (parameter 43.12). Continuous operation under this condition will lead to premature failure of the resistor and inability to dissipate regenerative energy, risking DC link overvoltage.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Check the warning limit setting in parameter 43.12 to ensure it is appropriate for the application.

  2. 4

    Verify that the brake resistor is correctly dimensioned for the application's braking energy requirements.

  3. 5

    Assess if the braking cycle frequency and duration meet the allowed limits for the installed resistor.

Source: ABB ACS580 General Purpose Drive