7121
Motor stall
ABB · ACS580 General Purpose Drive
What does 7121 mean?
The drive has tripped due to a motor stall condition. This fault is triggered when the motor current exceeds the stall current limit, and the output frequency or speed is below its set limit for a configured time. This indicates a severe overload or mechanical blockage, which can cause significant motor or drive damage if persistent.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Ensure the drive's stall detection parameters (31.25 Stall current limit, 31.26 Stall speed limit, 31.27 Stall frequency limit, 31.28 Stall time) are appropriately configured for the application.
Source: ABB ACS580 General Purpose Drive