Enable debug OFF
Project Download Failure - Debug Parameter OFF
ABB · AC500 Function Block Libraries
What does Enable debug OFF mean?
During project download to the safety CPU, the download process may stall at 0 bytes or an error message might appear because the "Enable debug" parameter was incorrectly set to "OFF" for the safety CPU configuration and then downloaded to the non-safety CPU.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Download the updated configuration to the non-safety CPU.
- 4
Download the new project code to the safety CPU using the AC500-S Programming Tool.
Source: ABB AC500 Function Block Libraries
View Official PDF